"Evaluation of the quality of electrical energy for an automation laboratory of Industry 4.0”

dc.creatorGuerra Chávez, Joseph Davides
dc.creatorGonzález Morales, Luises
dc.creatorRamos Valencia, Marco Vinicioes
dc.creatorBarrazueta Rojas, Sandraes
dc.date2021-06-21
dc.date.accessioned2025-11-10T19:41:19Z
dc.date.available2025-11-10T19:41:19Z
dc.descriptionThe research defines the energy quality and its parameters, based on ARCONEL 005/18 and 004/18, EN50160, IEC 61000-4-15 and IEEE 519-2014. Under this conception, an industry 4.0 automation laboratory was evaluated at the Escuela Superior Politécnica de Chimborazo. From the information obtained it was determined that the flicker values of Plt in phases B and C, exceeds the standard with 1.05% and 2.24%. The average total current harmonic distortion has values higher than the norm between 29.61% and 216.94%. The greatest distortion of individual current has phase B with odd harmonics from 3 to 11, with values between 46.22% to 9.14%. A total power factor of 0.83p.u was calculated below the norm. It´s concluded that to guarantee the quality of electrical energy, it´s regulations must be complied with and active filters incorporated in parallel.en
dc.descriptionEsta investigación define la calidad de energía y sus parámetros, basándose en las normativas ARCONEL 005/18 y 004/18, EN50160, IEC 61000-4-15 e IEEE 519-2014. Bajo esta concepción se evaluó un laboratorio de automatización de industria 4.0 en la Escuela Superior Politécnica de Chimborazo. De la información obtenida se determinó que los valores de flicker de Plt en las fases B y C, excede a la norma con el 1.05% y 2,24%. El promedio de la distorsión armónica de corriente total presenta valores superiores a la norma entre el 29.61% al 216.94%. La mayor distorsión de corriente individual presenta la fase B con armónicos impares del 3 al 11, con valores entre el 46,22% al 9,14%. Se calculó un factor de potencia total de 0,83p.u. inferior a la norma. Se concluye que para garantizar la calidad de energía eléctrica se debe acatar sus normativas e incorporar filtros activos en paralelo.  es
dc.formatapplication/pdf
dc.formattext/html
dc.identifierhttps://www.revistas.upse.edu.ec/index.php/rctu/article/view/558
dc.identifier10.26423/rctu.v8i1.558
dc.identifier.urihttps://repositorio.upse.edu.ec/handle/46000/14971
dc.languagespa
dc.publisherUniversidad Estatal Península de Santa Elenaes
dc.relationhttps://www.revistas.upse.edu.ec/index.php/rctu/article/view/558/495
dc.relationhttps://www.revistas.upse.edu.ec/index.php/rctu/article/view/558/508
dc.rightsDerechos de autor 2021 Revista Científica y Tecnológica UPSEes
dc.sourceUPSE Scientific and Technological Magazine; Vol. 8 No. 1 (2021): Edición Junio 2021; 56-67en
dc.sourceRevista Científica y Tecnológica UPSE; Vol. 8 Núm. 1 (2021): Edición Junio 2021; 56-67es
dc.source1390-7697
dc.source1390-7638
dc.source10.26423/rctu.v8i1
dc.subjectArmónicoses
dc.subjectCalidad de energía eléctricaes
dc.subjectNormativases
dc.subjectParámetros eléctricoses
dc.subjectVariables eléctricases
dc.subjectHarmonicsen
dc.subjectEnergy qualityen
dc.subjectStandardsen
dc.subjectElectrical parametersen
dc.subjectElectrical variablesen
dc.title"Evaluation of the quality of electrical energy for an automation laboratory of Industry 4.0”en
dc.titleEvaluación de la calidad de energía eléctrica para un laboratorio de automatización de Industria 4.0es
dc.typeinfo:eu-repo/semantics/article
dc.typeinfo:eu-repo/semantics/publishedVersion
dc.typeArtículo evaluado por pareses